Shown: a Metasol ACB; the ATS controller switches two interlocked ACBs.LS Electric ACB Automatic Transfer Switch Controller (ATSC) and ACB interlock ATS
Automatic transfer (changeover) controller for two interlocked ACBs
FMST lists 3 families of LS Electric controllers and circuit protectors (ACB ATS Controller, ACB Trip Relays and LCP Circuit Protector) with 10 models exactly as LS Electric’s English catalogues and website print them. FMST is an Authorized Partner & Distributor of LS Electric in Lahore.

LS Electric’s own photos, printed specifications and every order code. Tap a card for the full table.
Shown: a Metasol ACB; the ATS controller switches two interlocked ACBs.Automatic transfer (changeover) controller for two interlocked ACBs
Shown: a Susol ACB with its trip relay on the front.Electronic trip relay for Susol and Metasol air circuit breakers

Hydraulic-magnetic circuit protector for equipment, 0.1-30 A
Try another word, or search every LS Electric product.
All 3 families on this page, with the values LS Electric’s English catalogues and website print. Ranges are computed from plain printed numbers only; a dash means nothing is printed. WhatsApp 0306 4758850 to ask.
| Family | Models | Product | Source |
|---|---|---|---|
| LS Electric ACB Automatic Transfer Switch Controller (ATSC) and ACB interlock ATS | 2 | Automatic transfer (changeover) controller for two interlocked ACBs | Susol / Metasol ACB 2025.04, pp. 84–85 |
| LS Electric Susol / Metasol ACB Trip Relays (N, A, P, S type) | 4 | Electronic trip relay for Susol and Metasol air circuit breakers | Electric Products 2026.04, pp. 50–51 |
| LS Electric LCP Circuit Protector (CP) | 4 | Hydraulic-magnetic circuit protector for equipment, 0.1-30 A | Website, CP page |
The 10 rows of these families exactly as LS Electric’s English catalogues and website print them, column for column. Where a cell is misprinted, a short note under the table says so.
Automatic transfer (changeover) controller for two interlocked ACBs · 2 rows · LS Electric Susol / Metasol ACB catalogue (2025.04), pp. 84–85
| MODEL | Rated voltage | Voltage range | Frequency | Power consumption |
|---|---|---|---|---|
| ATSC-110 | AC 110V | AC 93.5 (±5%) ~ 126.5V (±5%) | 50Hz/60Hz | 15.4W |
| ATSC-220 | AC 220V | AC 187 (±5%) ~ 253V (±5%) | 50Hz/60Hz | 15.4W |
Electronic trip relay for Susol and Metasol air circuit breakers · 4 rows · LS Electric Electric Products catalogue (2026.04), pp. 50–51
| MODEL | Device label | Protection | Communication | Power supply | Other functions |
|---|---|---|---|---|---|
| N type | Smart Trip Unit | L/S/I/G | - | Self power | RTC timer mounted; fault indicator (LED); NFC |
| A type | Digital Trip Relay | L/S/I/G (or Gext); ZSI (protective coordination) | Modbus/RS-485; USB terminal (power, communication); Ethernet (optional product required) | Self power; AC/DC 100~250V; DC 24~48V | Remote reset; ERMS, local/remote DI (selectable); RTC timer; fault recording (127EA); fault wave recording (6EA) |
| P type | Smart Trip Unit | L(N)/S1/I/G (or Gext); thermal (linear hot start); UV1/OV1/RV/D/S(V)1/VU/IU; UF1/OF1/ROCOF/RP/RQ1/OP/OQ/UP; ZSI | USB terminal (power, communication); Modbus/RS-485; Bluetooth (option); Ethernet (optional product required) | Self power; AC/DC 100~250V; DC 24~48V | Measurement V/A/W/Wh/F/PF; remote reset; ERMS, local/remote DI (selectable); event recording (255EA); fault recording (127EA); fault wave (6EA) |
| S type | Smart Trip Unit | L(N)/S(1,2)/I/G (or Gext); thermal (linear hot start); UV(1,2)/OV(1,2)/RV/D/S(V)(1,2)/VU/IU; UF(1,2)/OF(1,2)/ROCOF/RP/RQ(1,2)/OP/OQ/UP; ZSI | USB terminal (power, communication); Modbus/RS-485; Bluetooth; Ethernet (optional product required); NFC | Self power; AC/DC 100~250V; DC 24~48V | Measurement V/A/W/Wh/F/PF; relay group control (A,B); remote reset; ERMS, local/remote, group A/B DI (selectable); event recording (255EA); fault recording (127EA); fault wave (6EA) |
Hydraulic-magnetic circuit protector for equipment, 0.1-30 A · 4 rows · LS Electric website, CP product page (accessed November 2026)
| MODEL | Poles | Rated insulation voltage Ui | Rated current | Rated breaking capacity IEC60947-2 (A) | Rated breaking capacity IEC60934 (A) | Mass (approx.) |
|---|---|---|---|---|---|---|
| LCP-31FM | 1 | 250V / 65V | 0.1, 0.3, 0.5, 1, 2, 3, 5, 7, 10, 15, 20, 25, 30A | 1500 | 2500 | 80g |
| LCP-32FM | 2 | 250V / 125V | 0.1, 0.3, 0.5, 1, 2, 3, 5, 7, 10, 15, 20, 25, 30A | 1500 | 2500 | 160g |
| LCP-33FM | 3 | 250V | 0.1, 0.3, 0.5, 1, 2, 3, 5, 7, 10, 15, 20, 25, 30A | 1500 | 2500 | 240g |
| LCP-32FI* | 2 | 250V / 125V | 2, 3, 5, 10, 15, 20, 30A | 1500 | 2500 | 160g |
The breaking capacities are printed without a unit on the product page; the asterisk on LCP-32FI* has no printed footnote.
The same products from every circuit breaker brand FMST supplies as an Authorized Partner & Distributor, on one page each.
FMST quotes LS Electric controllers and circuit protectors on request, because the rate depends on the model, rating and quantity. WhatsApp 0306 4758850 with the order code and FMST replies with the current rate.
ACB ATS Controller (2 models), ACB Trip Relays (4 models) and LCP Circuit Protector (4 models): 3 families and 10 models, each row as LS Electric’s English catalogues and website print it.
ACB ATS Controller (automatic transfer (changeover) controller for two interlocked ACBs), ACB Trip Relays (electronic trip relay for Susol and Metasol air circuit breakers) and LCP Circuit Protector (hydraulic-magnetic circuit protector for equipment, 0.1-30 A).
Yes. FMST (Finest Material Supplier & Traders) is an Authorized Partner & Distributor of LS Electric in Lahore, supplying genuine LS Electric controllers and circuit protectors to contractors, panel builders, developers and buyers across Pakistan. WhatsApp 0306 4758850 with your list.
WhatsApp the order codes from this page, or your load list, and FMST quotes genuine LS Electric. Electrical desk: 0306 4758850. All LS Electric categories: LS Electric circuit breakers.