LS Electric BK Series DIN-rail SPD (AC)
DIN-rail AC surge protective device, Class I / II / III
20–80 kA
FMST lists 4 families of LS Electric surge protective devices (BK DIN-rail SPD AC, BK DIN-rail SPD DC, SD SPD Disconnector and SP Box-type SPD) with 53 models exactly as LS Electric’s English catalogues and website print them. FMST is an Authorized Partner & Distributor of LS Electric in Lahore.




LS Electric’s own photos, printed specifications and every order code. Tap a card for the full table.

DIN-rail AC surge protective device, Class I / II / III
20–80 kA

DIN-rail DC surge protective device, Class II, 24-1500 V DC
1P, 2P, 3P · 20–40 kA

DIN-rail disconnector for surge protective devices
1, 2, 3, 4P · 20–80 kA

Enclosed (box) surge protective device for single- and three-phase systems
40–200 kA
Try another word, or search every LS Electric product.
All 4 families on this page, with the values LS Electric’s English catalogues and website print. Ranges are computed from plain printed numbers only; a dash means nothing is printed. WhatsApp 0306 4758850 to ask.
| Family | Models | Poles | Imax | Voltage | Standard | Source |
|---|---|---|---|---|---|---|
| LS Electric BK Series DIN-rail SPD (AC) | 11 | — | 20–80 kA | 385 (N-PE -), 385 (N-PE 255), 460 (N-PE 255), 275 | IEC 61643-11 / KS C IEC 61643-11 / UL1449 | Electric Products 2026.04, pp. 8–9 |
| LS Electric BK Series DIN-rail SPD (DC) | 6 | 1P, 2P, 3P | 20–40 kA | DC45, DC65, DC220, DC700, DC1200, DC1500 | IEC 61643-11 | Electric Products 2026.04, p. 10 |
| LS Electric SD Series SPD Disconnector | 5 | 1, 2, 3, 4P | 20–80 kA | 230/400V | — | Electric Products 2026.04, p. 11 |
| LS Electric SP Series Box-type SPD (SPL / SPT / SPY) | 31 | — | 40–200 kA | 275, 385, 320 | — | Electric Products 2026.04, pp. 12–15 |
The 53 rows of these families exactly as LS Electric’s English catalogues and website print them, column for column. Where a cell is misprinted, a short note under the table says so.
DIN-rail AC surge protective device, Class I / II / III · 11 rows · LS Electric Electric Products catalogue (2026.04), pp. 8–9
| MODEL | Test class | Poles | Rated voltage Un (V) | Uc (V) | Up (kV) | In (kA) | Imax (kA) | Iimp / Uoc | Accessory | Certification |
|---|---|---|---|---|---|---|---|---|---|---|
| BK05S-T3 | Class III | 2, 4P | 230/440 | 385 (N-PE -) | ≤0.8 | - | - | Uoc 10kV | AL | CE, UL, KS, S |
| BK10S-T2 | Class II | 1, 1+N, 2, 3, 3+N, 4P | 230/440 | 385 (N-PE 255) | ≤1.5 | 10 | 20 | - | AL | CE, UL, KS, S |
| BK20S-T2 | Class II | 1, 1+N, 2, 3, 3+N, 4P | 230/440 | 385 (N-PE 255) | ≤1.8 | 20 | 40 | - | AL | CE, UL, KS, S |
| BK30S-T2 | Class II | 1, 1+N, 2, 3, 3+N, 4P | 230/440 | 385 (N-PE 255) | ≤2.0 | 30 | 60 | - | AL | CE, UL |
| BK40S-T2 | Class II | 1, 1+N, 2, 3, 3+N, 4P | 230/440 | 385 (N-PE 255) | ≤2.5 | 40 | 80 | - | AL | CE, UL, KS, S |
| BK12S-T1 | Class I (built-in type) | 1, 1+N, 2, 3, 3+N, 4P | 230/440 | 385 (N-PE 255) | ≤2.5 | - | - | Iimp 12.5kA (10/350) | - | CE |
| BK10S-T2 (Uc 480V) | Class II | 1, 1+N, 2, 3, 3+N, 4P | 254/440 | 460 (N-PE 255) | ≤1.5 | 10 | 20 | - | AL | — |
| BK20S-T2 (Uc 480V) | Class II | 1, 1+N, 2, 3, 3+N, 4P | 254/440 | 460 (N-PE 255) | ≤2.0 | 20 | 40 | - | AL | — |
| BK30S-T2 (Uc 480V) | Class II | 1, 1+N, 2, 3, 3+N, 4P | 254/440 | 460 (N-PE 255) | ≤2.2 | 30 | 60 | - | AL | — |
| BK40S-T2 (Uc 480V) | Class II | 1, 1+N, 2, 3, 3+N, 4P | 254/440 | 460 (N-PE 255) | ≤2.5 | 40 | 80 | - | AL | — |
| BK12S-T2 (Uc 275V) | Class II | 1, 2, 3, 4P, 1+N, 3+N | 275 | 275 | ≤1.5 | 20 | 40 | - | AL | CE, KS, S |
The Uc 385 V, 480 V and 275 V tables print the same type names; the Uc is added to the model cell to keep the rows apart.
DIN-rail DC surge protective device, Class II, 24-1500 V DC · 6 rows · LS Electric Electric Products catalogue (2026.04), p. 10
| MODEL | Poles | Rated voltage Un | Uc | Up (kV) | In (kA) | Imax (kA) | SPD disconnector MCCB | SPD disconnector MCB |
|---|---|---|---|---|---|---|---|---|
| BK10S-DC24 | 1P | DC24 | DC45 | ≤0.4 | 10 | 20 | - | - |
| BK10S-DC48 | 1P | DC48 | DC65 | ≤0.5 | 10 | 20 | - | - |
| BK20S-DC110 | 2P | DC110 | DC220 | ≤1.0 | 20 | 40 | TD100 2P 32A | BK63H-DC 2P 40A |
| BK20S-DC600 | 3P | DC600 | DC700 | ≤2.5 | 20 | 40 | TD100 3P 32A | BK63H-DC 3P 40A |
| BK20S-DC1000 | 3P | DC1000 | DC1200 | ≤3.9 | 20 | 40 | TD100 4P 32A | BK63H-DC 4P 40A |
| BK20S-DC1500 | 3P | DC1500 | DC1500 | ≤4.5 | 20 | 40 | TSD250N/H 4P 63A | - |
DIN-rail disconnector for surge protective devices · 5 rows · LS Electric Electric Products catalogue (2026.04), p. 11
| MODEL | Test class | Up (kV) | In (kA) | Imax (kA) | Iimp (kA) |
|---|---|---|---|---|---|
| SD10-T2 | Class II, III | 0.25 | 10 | 20 | - |
| SD20-T2 | Class II | 0.4 | 20 | 40 | - |
| SD30-T2 | Class II | 0.5 | 30 | 60 | - |
| SD40-T2 | Class II | 0.7 | 40 | 80 | - |
| SD13-T1 | Class I | 0.3 | - | - | 12.5kA |
Enclosed (box) surge protective device for single- and three-phase systems · 31 rows · LS Electric Electric Products catalogue (2026.04), pp. 12–15
| MODEL | Class | Rated system | Rated voltage Un | Uc (V AC) | Up (kV) | In (kA) | Imax (kA) | Iimp 10/350 (kA) | Protection mode |
|---|---|---|---|---|---|---|---|---|---|
| SPL3-20S | Class III | 2W+G (single phase) | AC 110, 220 | 275 | 1.5 | - | - | - | L-N, N-PE (G), L-PE (G) |
| SPL2-40S | Class II | 2W+G (single phase) | AC 220 | 385 | 2.5 | 20 | 40 | - | L-N, N-PE (G) |
| SPL2-80S | Class II | 2W+G (single phase) | AC 220 | 385 | 3.0 | 40 | 80 | - | L-N, N-PE (G) |
| SPT2-40S (AC 220V) | Class II | 3W+G | AC 220 | 385 | 2.5 | 20 | 40 | - | L-PE (G) |
| SPT2-80S (AC 220V) | Class II | 3W+G | AC 220 | 385 | 3.0 | 40 | 80 | - | L-PE (G) |
| SPT1-120S (AC 220V) | Class I, Class II | 3W+G | AC 220 | 385 | 2.0 | - | 120 | 6.5 | L-PE (G) |
| SPT1-160S (AC 220V) | Class I, Class II | 3W+G | AC 220 | 385 | 2.0 | - | 160 | 6.5 | L-PE (G) |
| SPT2-40S (AC 380V) | Class II | 3W+G | AC 380 | 385 | 2.5 | 20 | 40 | - | L-PE (G) |
| SPT2-80S (AC 380V) | Class II | 3W+G | AC 380 | 385 | 3.0 | 40 | 80 | - | L-PE (G) |
| SPT1-120S (AC 380V) | Class I, Class II | 3W+G | AC 380 | 385 | 2.0 | - | 120 | 6.5 | L-PE (G) |
| SPT1-160S (AC 380V) | Class I, Class II | 3W+G | AC 380 | 385 | 2.0 | - | 160 | 6.5 | L-PE (G) |
| SPT2-40S (AC 440V) | Class II | 3W+G | AC 440 | 385 | 2.5 | 20 | 40 | - | L-PE (G) |
| SPT2-80S (AC 440V) | Class II | 3W+G | AC 440 | 385 | 3.0 | 40 | 80 | - | L-PE (G) |
| SPT1-120S (AC 440V) | Class I, Class II | 3W+G | AC 440 | 385 | 2.0 | - | 120 | 6.5 | L-PE (G) |
| SPT1-160S (AC 440V) | Class I, Class II | 3W+G | AC 440 | 385 | 2.0 | - | 160 | 6.5 | L-PE (G) |
| SPY2-40S (AC 127/220V) | Class II | 4W+G | AC 127/220 | 385 | 2.5 | 20 | 40 | - | L-N, N-PE (G) |
| SPY2-80S (AC 127/220V) | Class II | 4W+G | AC 127/220 | 385 | 3.0 | 40 | 80 | - | L-N, N-PE (G) |
| SPY1-120S (AC 127/220V) | Class I, Class II | 4W+G | AC 127/220 | 385 | 2.0 | - | 120 | 6.5 | L-N, N-PE (G) |
| SPY1-160S (AC 127/220V) | Class I, Class II | 4W+G | AC 127/220 | 385 | 2.0 | - | 160 | 6.5 | L-N, N-PE (G) |
| SPY1-200S (AC 127/220V) | Class I, Class II | 4W+G | AC 127/220 | 385 | 2.0 | - | 200 | 12.5 | L-N, N-PE (G) |
| SPY2-40S (AC 220/380V) | Class II | 4W+G | AC 220/380 | 385 | 2.5 | 20 | 40 | - | L-N, N-PE (G) |
| SPY2-80S (AC 220/380V) | Class II | 4W+G | AC 220/380 | 385 | 3.0 | 40 | 80 | - | L-N, N-PE (G) |
| SPY1-120S (AC 220/380V) | Class I, Class II | 4W+G | AC 220/380 | 385 | 2.0 | - | 120 | 6.5 | L-N, N-PE (G) |
| SPY1-160S (AC 220/380V) | Class I, Class II | 4W+G | AC 220/380 | 385 | 2.0 | - | 160 | 6.5 | L-N, N-PE (G) |
| SPY1-200S (AC 220/380V) | Class I, Class II | 4W+G | AC 220/380 | 385 | 2.0 | - | 200 | 12.5 | L-N, N-PE (G) |
| SPL1-25/50S | Class I | 2W+G | AC 220 | 320 | L-N 1.3, N-PE 2.0 | - | - | 25/50 | N-PE (G) |
| SPT1-25S | Class I | 3W+G | AC 380 | 320 | L-N 1.3, N-PE 2.0 | - | - | 25 | L-PE (G) |
| SPY1-25/100S | Class I | 4W+G | AC 380/220 | 320 | L-N 1.3, N-PE 2.0 | - | - | 25/100 | L-N, N-PE (G) |
| SPL1-13/50S | Class I | 2W+G | AC 220 | 320 | L-N 1.2, N-PE 1.8 | - | - | 12.5/50 | L-N, N-PE (G) |
| SPT1-13S | Class I | 3W+G | AC 220 | 320 | L-N 1.2, N-PE 1.8 | - | - | 12.5 | L-PE (G) |
| SPY1-13/50S | Class I | 4W+G | AC 380/220 | 320 | L-N 1.2, N-PE 1.8 | - | - | 12.5/50 | L-N, N-PE (G) |
The same SPT and SPY type names are printed in separate tables per system voltage; the voltage is added to the model cell.
The same products from every circuit breaker brand FMST supplies as an Authorized Partner & Distributor, on one page each.
FMST quotes LS Electric surge protective devices on request, because the rate depends on the model, rating and quantity. WhatsApp 0306 4758850 with the order code and FMST replies with the current rate.
BK DIN-rail SPD AC (11 models), BK DIN-rail SPD DC (6 models), SD SPD Disconnector (5 models) and SP Box-type SPD (31 models): 4 families and 53 models, each row as LS Electric’s English catalogues and website print it.
Imax is the largest surge current (8/20 µs wave) the device can discharge; Uc is the highest voltage it can stay connected to continuously. As printed: BK DIN-rail SPD AC 20–80 kA, 385 (N-PE -), 385 (N-PE 255), 460 (N-PE 255), 275; BK DIN-rail SPD DC 20–40 kA, DC45, DC65, DC220, DC700, DC1200, DC1500; SD SPD Disconnector 20–80 kA, 230/400V; SP Box-type SPD 40–200 kA, 275, 385, 320.
Yes. FMST (Finest Material Supplier & Traders) is an Authorized Partner & Distributor of LS Electric in Lahore, supplying genuine LS Electric surge protective devices to contractors, panel builders, developers and buyers across Pakistan. WhatsApp 0306 4758850 with your list.
WhatsApp the order codes from this page, or your load list, and FMST quotes genuine LS Electric. Electrical desk: 0306 4758850. All LS Electric categories: LS Electric circuit breakers.