Terasaki TemPower2 Air Circuit Breakers
Air circuit breaker (fixed or draw-out)
3P, 4P · 800–6,300 A · 65–135 kA
FMST lists 4 families of Terasaki air circuit breakers (TemPower2, TemPower2 Economical, TemPower2 DC and TemPower PRO) with 75 models exactly as Terasaki’s own catalogues and product pages print them. FMST is an Authorized Partner & Distributor of Terasaki in Lahore.




Terasaki’s own photos, printed specifications and every order code. Tap a card for the full table.

Air circuit breaker (fixed or draw-out)
3P, 4P · 800–6,300 A · 65–135 kA

Air circuit breaker, economical series, fixed type
3P, 4P · 630–1,600 A · 50 kA

DC air circuit breaker
3P, 4P · 800–4,000 A · 40/40 kA (DC600V; AR325-NDH at DC800V)

Compact air circuit breaker (AX series), standard and high-fault types
3P, 4P · 630–2,000 A · 50–66 kA
Try another word, or search every Terasaki product.
All 4 families on this page, with the values Terasaki’s own catalogues and product pages print. Ranges are computed from plain printed numbers only; a dash means nothing is printed. WhatsApp 0306 4758850 to ask.
| Family | Models | Poles | Rated current | Frames | Breaking capacity | Trip unit | Source |
|---|---|---|---|---|---|---|---|
| Terasaki TemPower2 Air Circuit Breakers | 38 | 3P, 4P | 800–6,300 A | 800, 1,250, 1,600, 2,000, 2,500, 3,200, 4,000, 5,000, 6,300 A | 65–135 kA | AGR-11B, AGR-21B, AGR-22B, AGR-31B (catalogue 18-I55E) | TemPower2 air circuit breakers page |
| Terasaki TemPower2 Economical series Air Circuit Breakers | 5 | 3P, 4P | 630–1,600 A | — | 50 kA | — | Catalogue 10-I56E, p. 3 |
| Terasaki TemPower2 Air Circuit Breakers for DC Special Voltage | 8 | 3P, 4P | 800–4,000 A | 800, 1,250, 1,600, 2,000, 2,500, 3,200, 4,000 A | 40/40 kA (DC600V; AR325-NDH at DC800V) | — | TemPower2 DC special voltage page |
| Terasaki TemPower PRO Air Circuit Breakers | 24 | 3P, 4P | 630–2,000 A | 630, 800, 1,000, 1,250, 1,600, 2,000 A | 50–66 kA | — | TemPower PRO page |
The 75 rows of these families exactly as Terasaki’s own catalogues and product pages print them, column for column. Where a cell is misprinted, a short note under the table says so.
Air circuit breaker (fixed or draw-out) · 38 rows · Terasaki’s TemPower2 air circuit breakers page, ratings and specifications table (catalogue 18-I55E) · accessories: TemPower2 ACB Accessories
| Model | Frame [A] | Poles | Rated current (max) [A] | RATED PRIMARY CURRENT OF OVER-CURRENT RELEASE (ICT) [A] | Rated breaking capacity [kA sym rms] / Rated making capacity [kA peak] (AC440V) (Ics=Icu) | Rated short time withstand current Icw [kA] | Outline dimensions [mm] (WxHxD) | Weight [kg] |
|---|---|---|---|---|---|---|---|---|
| AR208S | 800 | 3 | 800 | 200,400,800 | 65/143 * | 1sec 65 / 3sec 50 | Fixed type 360×460×290 / Draw-out type 354×460×345 | 73 |
| AR208S | 800 | 4 | 800 | 200,400,800 | 65/143 * | 1sec 65 / 3sec 50 | Fixed type 445×460×290 / Draw-out type 439×460×345 | 86 |
| AR212S | 1250 | 3 | 1250 | 400,800,1000,1250 | 65/143 * | 1sec 65 / 3sec 50 | Fixed type 360×460×290 / Draw-out type 354×460×345 | 73 |
| AR212S | 1250 | 4 | 1250 | 400,800,1000,1250 | 65/143 * | 1sec 65 / 3sec 50 | Fixed type 445×460×290 / Draw-out type 439×460×345 | 86 |
| AR212H | 1250 | 3 | 1250 | 200,400,800,1000,1250 | 80/176 | 1sec 80 / 3sec 55 | Fixed type 360×460×290 / Draw-out type 354×460×345 | 79 |
| AR212H | 1250 | 4 | 1250 | 200,400,800,1000,1250 | 80/176 | 1sec 80 / 3sec 55 | Fixed type 445×460×290 / Draw-out type 439×460×345 | 94 |
| AR216S | 1600 | 3 | 1600 | 400,800,1000,1250,1600 | 65/143 * | 1sec 80 / 3sec 55 | Fixed type 360×460×290 / Draw-out type 354×460×345 | 76 |
| AR216S | 1600 | 4 | 1600 | 400,800,1000,1250,1600 | 65/143 * | 1sec 80 / 3sec 55 | Fixed type 445×460×290 / Draw-out type 439×460×345 | 90 |
| AR216H | 1600 | 3 | 1600 | 1600 | 80/176 | 1sec 80 / 3sec 55 | Fixed type 360×460×290 / Draw-out type 354×460×345 | 79 |
| AR216H | 1600 | 4 | 1600 | 1600 | 80/176 | 1sec 80 / 3sec 55 | Fixed type 445×460×290 / Draw-out type 439×460×345 | 94 |
| AR316H | 1600 | 3 | 1600 | 200,400,800,1250,1600 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 466×460×290 / Draw-out type 460×460×345 | 105 |
| AR316H | 1600 | 4 | 1600 | 200,400,800,1250,1600 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 586×460×290 / Draw-out type 580×460×345 | 125 |
| AR220S | 2000 | 3 | 2000 | 400,800,1000,1250,1600,2000 | 65/143 * | 1sec 65 / 3sec 50 | Fixed type 360×460×290 / Draw-out type 354×460×345 | 79 |
| AR220S | 2000 | 4 | 2000 | 400,800,1000,1250,1600,2000 | 65/143 * | 1sec 65 / 3sec 50 | Fixed type 445×460×290 / Draw-out type 439×460×345 | 94 |
| AR220H | 2000 | 3 | 2000 | 2000 | 80/176 | 1sec 80 / 3sec 55 | Fixed type 360×460×290 / Draw-out type 354×460×345 | 79 |
| AR220H | 2000 | 4 | 2000 | 2000 | 80/176 | 1sec 80 / 3sec 55 | Fixed type 445×460×290 / Draw-out type 439×460×345 | 94 |
| AR320H | 2000 | 3 | 2000 | 2000 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 466×460×290 / Draw-out type 460×460×345 | 105 |
| AR320H | 2000 | 4 | 2000 | 2000 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 586×460×290 / Draw-out type 580×460×345 | 125 |
| AR420H | 2000 | 3 | 2000 | 800,2000 | 120/264 | 1sec 100 / 3sec 85 | Fixed type - / Draw-out type 631×460×375 | 147 |
| AR325S | 2500 | 3 | 2500 | 2500 | 85/187 * | 1sec 85 / 3sec 65 | Fixed type 466×460×290 / Draw-out type 460×460×345 | 105 |
| AR325S | 2500 | 4 | 2500 | 2500 | 85/187 * | 1sec 85 / 3sec 65 | Fixed type 586×460×290 / Draw-out type 580×460×345 | 125 |
| AR325H | 2500 | 3 | 2500 | 2500 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 466×460×290 / Draw-out type 460×460×345 | 105 |
| AR325H | 2500 | 4 | 2500 | 2500 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 586×460×290 / Draw-out type 580×460×345 | 125 |
| AR332S | 3200 | 3 | 3200 | 3200 | 85/187 * | 1sec 85 / 3sec 65 | Fixed type 466×460×290 / Draw-out type 460×460×345 | 105 |
| AR332S | 3200 | 4 | 3200 | 3200 | 85/187 * | 1sec 85 / 3sec 65 | Fixed type 586×460×290 / Draw-out type 580×460×345 | 125 |
| AR332H | 3200 | 3 | 3200 | 3200 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 466×460×290 / Draw-out type 460×460×345 | 105 |
| AR332H | 3200 | 4 | 3200 | 3200 | 100/220 | 1sec 100 / 3sec 75 | Fixed type 586×460×290 / Draw-out type 580×460×345 | 125 |
| AR440SB | 4000 | 3 | 4000 | 4000 | 100/220 | 1sec 100 / 3sec 75 | Fixed type - / Draw-out type 460×460×345 | 126 |
| AR440SB | 4000 | 4 | 4000 | 4000 | 100/220 | 1sec 100 / 3sec 75 | Fixed type - / Draw-out type 580×460×345 | 158 |
| AR440S | 4000 | 3 | 4000 | 4000 | 100/220 | 1sec 100 / 3sec 85 | Fixed type - / Draw-out type 631×460×375 | 139 |
| AR440S | 4000 | 4 | 4000 | 4000 | 100/220 | 1sec 100 / 3sec 85 | Fixed type - / Draw-out type 801×460×375 | 176 |
| AR440H | 4000 | 3 | 4000 | 4000 | 120/264 | 1sec 100 / 3sec 85 | Fixed type - / Draw-out type 631×460×375 | 147 |
| AR650S | 5000 | 3 | 5000 | 5000 | 120/264 | 1sec 120 / 3sec 85 | Fixed type - / Draw-out type 799×460×380 | 200 |
| AR650S | 5000 | 4 | 5000 | 5000 | 120/264 | 1sec 120 / 3sec 85 | Fixed type - / Draw-out type 1034×460×380 | 260 |
| AR663S | 6300 | 3 | 6300 | 6300 | 120/264 | 1sec 120 / 3sec 85 | Fixed type - / Draw-out type 799×460×380 | 220 |
| AR663S | 6300 | 4 | 6300 | 6300 | 120/264 | 1sec 120 / 3sec 85 | Fixed type - / Draw-out type 1034×460×380 | 285 |
| AR663H | 6300 | 3 | 5000,6300 | 6300 | 135/297 | 1sec 120 / 3sec 85 | Fixed type - / Draw-out type 799×460×380 | 220 |
| AR663H | 6300 | 4 | 5000,6300 | 6300 | 135/297 | 1sec 120 / 3sec 85 | Fixed type - / Draw-out type 1034×460×380 | 285 |
* after a breaking capacity: “The value at 500Vac.” (Terasaki’s footnote). Short-time withstand at 1 s and 3 s, and the fixed and draw-out dimensions, are joined with a slash.
Air circuit breaker, economical series, fixed type · 5 rows · Terasaki TemPower2 Economical series catalogue 10-I56E, ratings page (p. 3)
| Model | Ampere rating [A] | Rated current (max) In [A] | Poles | Rated current of over-current release In [A] | Rated operational voltage Ue [V] | Breaking/making capacity AC690V [kA sym rms / kA peak] (Ics=Icu) | Breaking/making capacity AC440V [kA sym rms / kA peak] (Ics=Icu) | Icw 0.5s [kA] | Icw 1s [kA] | Mass 3P / 4P [kg] | Outline, fixed type a x b x c (d) [mm] |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AR206E | 630 | 630 | 3 / 4 | 630 | 690 | 30/63 | 50/105 | 50 | 42 | 35 / 42 | 356 / 441 x 460 x 272 (d 63) |
| AR208E | 800 | 800 | 3 / 4 | 800 | 690 | 30/63 | 50/105 | 50 | 42 | 35 / 42 | 356 / 441 x 460 x 272 (d 63) |
| AR210E | 1000 | 1000 | 3 / 4 | 1000 | 690 | 30/63 | 50/105 | 50 | 42 | 35 / 42 | 356 / 441 x 460 x 272 (d 63) |
| AR212E | 1250 | 1250 | 3 / 4 | 1250 | 690 | 30/63 | 50/105 | 50 | 42 | 38 / 45 | 356 / 441 x 460 x 272 (d 63) |
| AR216E | 1600 | 1600 | 3 / 4 | 1600 | 690 | 30/63 | 50/105 | 50 | 42 | 38 / 45 | 356 / 441 x 460 x 272 (d 63) |
DC air circuit breaker · 8 rows · Terasaki’s TemPower2 DC special voltage page, ratings and specifications table (catalogue 18-I73E)
| Model | Frame [A] | Poles | Rated current [A] | Rated breaking capacity [kA] Icu/Ics (DC600V) / Rated breaking capacity [kA] Icu/Ics (DC800V) | Rated short time withstand current Icw [kA/1sec] | Outline dimensions [mm] (WxHxD) | Weight [kg] |
|---|---|---|---|---|---|---|---|
| AR208S | 800 | 3 | 800 | 40/40 | 40 | 354×460×354 | 76 |
| AR212S | 1250 | 3 | 1250 | 40/40 | 40 | 354×460×354 | 76 |
| AR216S | 1600 | 3 | 1600 | 40/40 | 40 | 354×460×354 | 76 |
| AR220S | 2000 | 3 | 2000 | 40/40 | 40 | 354×460×354 | 79 |
| AR325S | 2500 | 3 | 2500 | 40/40 | 40 | 460×460×354 | 105 |
| AR332S | 3200 | 3 | 3200 | 40/40 | 40 | 460×460×354 | 105 |
| AR440S | 4000 | 3 | 4000 | 40/40 | 40 | 631×460×375 | 139 |
| AR325-NDH | 2500 | 4 | 2500 | 40/40 | 30 | 580×460×354 | 125 |
Compact air circuit breaker (AX series), standard and high-fault types · 24 rows · Terasaki’s TemPower PRO page, ratings and specifications table (catalogue 25-I58E) · accessories: TemPower PRO ACB Accessories
| Model | Series | Frame [A] | Poles | Maximum rated current [A] | Rated primary current of over-current release | Rated breaking capacity [kA sym rms]/ Rated making capacity [KA peak] (AC440V) ICU | Rated breaking capacity [kA sym rms]/ Rated making capacity [KA peak] (AC440V) ICS | Rated short time withstand current ICW[kA] | Outline dimensions [mm] (W x H x D) | Weight [kg] for draw-out type |
|---|---|---|---|---|---|---|---|---|---|---|
| AX106S | Standard type | 630 | 3 | 630 | 400, 630 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX106S | Standard type | 630 | 4 | 630 | 400, 630 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX108S | Standard type | 800 | 3 | 800 | 800 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX108S | Standard type | 800 | 4 | 800 | 800 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX110S | Standard type | 1000 | 3 | 1000 | 1000 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX110S | Standard type | 1000 | 4 | 1000 | 1000 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX112S | Standard type | 1250 | 3 | 1250 | 1250 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX112S | Standard type | 1250 | 4 | 1250 | 1250 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX116S | Standard type | 1600 | 3 | 1600 | 1600 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX116S | Standard type | 1600 | 4 | 1600 | 1600 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX120S | Standard type | 2000 | 3 | 2000 | 2000 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 276 x 312.5 x 279 / Draw-out type - | 37 |
| AX120S | Standard type | 2000 | 4 | 2000 | 2000 | 50/105 | 50/105 | 1s 50 / 3s 24 | Fixed type 276 x 312.5 x 279 / Draw-out type - | 45 |
| AX106H | High fault type | 630 | 3 | 630 | 400, 630 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX106H | High fault type | 630 | 4 | 630 | 400, 630 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX108H | High fault type | 800 | 3 | 800 | 800 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX108H | High fault type | 800 | 4 | 800 | 800 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX110H | High fault type | 1000 | 3 | 1000 | 1000 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX110H | High fault type | 1000 | 4 | 1000 | 1000 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX112H | High fault type | 1250 | 3 | 1250 | 1250 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX112H | High fault type | 1250 | 4 | 1250 | 1250 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX116H | High fault type | 1600 | 3 | 1600 | 1600 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX116H | High fault type | 1600 | 4 | 1600 | 1600 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX120H | High fault type | 2000 | 3 | 2000 | 2000 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 276 x 312.5 x 279 / Draw-out type - | 18 *Note:1) |
| AX120H | High fault type | 2000 | 4 | 2000 | 2000 | 66/145.2 | 55/121 | 1s 55 / 3s 30 | Fixed type 276 x 312.5 x 279 / Draw-out type - | 22 *Note:1) |
Short-time withstand at 1 s and 3 s, and the fixed and draw-out dimensions, are joined with a slash.
The same products from every circuit breaker brand FMST supplies as an Authorized Partner & Distributor, on one page each.
FMST quotes Terasaki air circuit breakers on request, because the rate depends on the model, rating and quantity. WhatsApp 0306 4758850 with the order code (for example AR208S and AR206E) and FMST replies with the current rate.
TemPower2 (38 models), TemPower2 Economical (5 models), TemPower2 DC (8 models) and TemPower PRO (24 models): 4 families and 75 models, each row as Terasaki’s own catalogues and product pages print it.
As printed: TemPower2: 800–6,300 A in 800, 1,250, 1,600, 2,000, 2,500, 3,200, 4,000, 5,000, 6,300 A frames, 65–135 kA, 3P, 4P; TemPower2 Economical: 630–1,600 A, 50 kA, 3P, 4P; TemPower2 DC: 800–4,000 A in 800, 1,250, 1,600, 2,000, 2,500, 3,200, 4,000 A frames, 40/40 kA (DC600V; AR325-NDH at DC800V), 3P, 4P; TemPower PRO: 630–2,000 A in 630, 800, 1,000, 1,250, 1,600, 2,000 A frames, 50–66 kA, 3P, 4P.
Yes. FMST (Finest Material Supplier & Traders) is an Authorized Partner & Distributor of Terasaki in Lahore, supplying genuine Terasaki air circuit breakers to contractors, panel builders, developers and buyers across Pakistan. WhatsApp 0306 4758850 with your list.
WhatsApp the order codes from this page, or your load list, and FMST quotes genuine Terasaki. Electrical desk: 0306 4758850. All Terasaki categories: Terasaki circuit breakers.