Terasaki TemBreak PRO Switch-disconnectors
Moulded case switch-disconnector (no overcurrent trip)
2P, 3P, 4P · 30–1,600 A
FMST lists 6 families of Terasaki switch-disconnectors and non-automatic breakers (TemBreak PRO Switch-disconnectors, TemBreak PRO European Switch disconnectors, TemBreak PRO Non-automatic trip breakers, TemBreak PRO Switch-disconnectors 600-1000 V DC, TemPower PRO Switch Disconnectors and TemBreak 2 Switch-Disconnectors) with 65 models exactly as Terasaki’s own catalogues and product pages print them. FMST is an Authorized Partner & Distributor of Terasaki in Lahore.




Terasaki’s own photos, printed specifications and every order code. Tap a card for the full table.

Moulded case switch-disconnector (no overcurrent trip)
2P, 3P, 4P · 30–1,600 A

Moulded case switch-disconnector
3P, 4P · 160–1,600 A

Moulded case switch (circuit breaker without overcurrent trip mechanism)
3P, 4P · 2,000–3,200 A

DC moulded case switch-disconnector
3P, 4P · 160–800 A

Air switch-disconnector (AX…D)
3P, 4P · 630–1,600 A
Shown: a TemBreak 2 MCCB; the switch-disconnectors share its moulded case frames.Moulded case switch-disconnector (type NN, no protection)
3P, 4P · 125–1,600 A
Try another word, or search every Terasaki product.
All 6 families on this page, with the values Terasaki’s own catalogues and product pages print. Ranges are computed from plain printed numbers only; a dash means nothing is printed. WhatsApp 0306 4758850 to ask.
| Family | Models | Poles | Rated current | Breaking capacity | Voltage | Product | Source |
|---|---|---|---|---|---|---|---|
| Terasaki TemBreak PRO Switch-disconnectors | 20 | 2P, 3P, 4P | 30–1,600 A | — | up to AC690V / DC250V | Moulded case switch-disconnector (no overcurrent trip) | TemBreak PRO Switch-disconnectors page |
| Terasaki TemBreak PRO European Switch disconnectors | 10 | 3P, 4P | 160–1,600 A | — | AC690V, DC250V | Moulded case switch-disconnector | European series page |
| Terasaki TemBreak PRO Non-automatic trip breakers | 3 | 3P, 4P | 2,000–3,200 A | — | — | Moulded case switch (circuit breaker without overcurrent trip mechanism) | TemBreak PRO Non-automatic trip breakers page |
| Terasaki TemBreak PRO Switch-disconnectors for 600-1000 V DC | 13 | 3P, 4P | 160–800 A | — | DC600V - DC1000V | DC moulded case switch-disconnector | TemBreak PRO 600-1000 V DC switch-disconnectors page |
| Terasaki TemPower PRO Switch Disconnectors | 10 | 3P, 4P | 630–1,600 A | — | — | Air switch-disconnector (AX…D) | TemPower PRO page |
| Terasaki TemBreak 2 Switch-Disconnectors | 9 | 3P, 4P | 125–1,600 A | — | — | Moulded case switch-disconnector (type NN, no protection) | Catalogue 18-I61E, pp. 21-22 |
The 65 rows of these families exactly as Terasaki’s own catalogues and product pages print them, column for column. Where a cell is misprinted, a short note under the table says so.
Moulded case switch-disconnector (no overcurrent trip) · 20 rows · Terasaki’s TemBreak PRO Switch-disconnectors page, ratings and specifications table (catalogue 23-I68E) · accessories: TemBreak PRO Accessories, TemBreak PRO Motor Operators, TemPlug70
| Model | Frame [A] | Poles | Rated current [A] | Rated operational voltage | Rated short circuit making capacity Icm [kA peak] | Rated short time withstand current Icw [kA] | Utilization category IEC60947-3 | Upstream breaker (OPCD) | Outline dimensions [mm] (WxHxD) | Weight [kg] |
|---|---|---|---|---|---|---|---|---|---|---|
| PE30-NN | 30 | 2 / 3 | 30 | AC415V | 1.5 | 1 (1sec) | AC-23A | PE30-NF | 50×130×68 / 75×130×68 | 0.5 / 0.7 |
| PE50-NN | 50 | 2 / 3 | 50 | AC500V,DC250V / AC500V | 1.5 | 1 (1sec) | AC-23A, DC-22A / AC-23A | PE50-NF | 50×130×68 / 75×130×68 | 0.5 / 0.7 |
| PE125-NN | 100 | 2 / 3 | 100 | AC500V,DC250V / AC500V | 2.13 | 1.5 (0.3sec) | AC-23A, DC-22A / AC-23A | PE50-NF | 50×130×68 / 75×130×68 | 0.5 / 0.7 |
| PE125-NN | 125 | 2 / 3 | 125 | AC500V,DC250V / AC500V | 2.13 | 1.5 (0.3sec) | AC-23A, DC-22A / AC-23A | PE50-NF | 50×130×68 / 75×130×68 | 0.5 / 0.7 |
| S125-SN | 100 | 3 / 4 | 100 | AC690V / DC250V | 2.8 | 2 (0.3sec) | AC-23A / DC-22A | S125-SF | 75×130×68 / 100×130×68 | 0.7 / 0.9 |
| S125-SN | 125 | 3 / 4 | 125 | AC690V / DC250V | 2.8 | 2 (0.3sec) | AC-23A / DC-22A | S125-SF | 75×130×68 / 100×130×68 | 0.7 / 0.9 |
| PS125-NN | 100 | 3 / 4 | 100 | AC690V / DC250V | 2.8 | 2 (1sec) | AC-23A / DC-22A | PS125-NF | 90×130×68 / 120×130×68 | 1.0 / 1.3 |
| PS125-NN | 125 | 3 / 4 | 125 | AC690V / DC250V | 2.8 | 2 (1sec) | AC-23A / DC-22A | PS125-NF | 90×130×68 / 120×130×68 | 1.0 / 1.3 |
| S250-SN | 225 | 3 / 4 | 225 | AC690V / DC250V | 6 | 3 (0.3sec) | AC-23A / DC-22A | E250-SF | 105×165×68 / 140×165×68 | 1.5 / 1.9 |
| S250-SN | 250 | 3 / 4 | 250 | AC690V / DC250V | 6 | 3 (0.3sec) | AC-23A / DC-22A | E250-SF | 105×165×68 / 140×165×68 | 1.5 / 1.9 |
| S250-NN | 225 | 3 / 4 | 225 | AC690V / DC250V | 5 | 3 (0.3sec) | AC-23A / DC-22A | PS250-NF | 105×165×68 / 140×165×68 | 1.5 / 2.0 |
| S250-NN | 250 | 3 / 4 | 250 | AC690V / DC250V | 5 | 3 (0.3sec) | AC-23A / DC-22A | PS250-NF | 105×165×68 / 140×165×68 | 1.5 / 2.0 |
| PS400-NN | 400 | 3 / 4 | 400 | AC690V / DC250V | 7.6 | 5 (1sec) | AC-23A / DC-22A | PS400-NF | 140×260×103 / 185×260×103 | 5.4 / 7.2 |
| PS630-NN | 600 | 3 / 4 | 600 | AC690V / DC250V | 13 | 7.6 (1sec) | AC-22A / DC-22A | PS630-NF | 140×260×103 / 185×260×103 | 5.7 / 7.7 |
| S630-GN | 600 | 3 / 4 | 600 | AC690V / DC250V | 17 | 10 (0.3sec) | AC-23A / DC-22A | S630-NF | 210×273×103 / 280×273×103 | 8.0 / 11.0 |
| S630-GN | 630 | 3 / 4 | 630 | AC690V / DC250V | 17 | 10 (0.3sec) | AC-23A / DC-22A | S630-NF | 210×273×103 / 280×273×103 | 8.0 / 11.0 |
| S800-NN | 800 | 3 / 4 | 800 | AC690V / DC250V | 17 | 10 (0.3sec) | AC-23A / DC-22A | S800-NF | 210×273×103 / 280×273×103 | 8.5 / 11.5 |
| S1000-NN | 1000 | 3 / 4 | 1000 | AC690V / DC250V | 17 | 10 (0.3sec) | AC-23A / DC-22A | S1000-CE | 210×273×103 / 280×273×103 | 10.4 / 14.0 |
| S1250-NN | 1250 | 3 / 4 | 1250 | AC690V / DC250V | 32 | 15 (0.3sec) | AC-23A / DC-22A | S1250-NE | 210×370×120 / 280×370×120 | 18.2 / 23.4 |
| S1600-NN | 1600 | 3 / 4 | 1600 | AC690V / DC250V | 45 | 20 (0.3sec) | AC-23A / DC-22A | S1600-NE | 210×370×140 / 280×370×140 | 24.9 / 32.9 |
Where a type is printed on two sub-rows, the values are joined with a slash: AC690V and DC250V are the two voltage ratings of the type. PS630-NN 3-pole is printed AC-22A; the other AC rows print AC-23A.
Moulded case switch-disconnector · 10 rows · Terasaki’s TemBreak PRO European series page, switch disconnectors, ratings and specifications table (catalogue 23-I68EJ)
| Model | Frame [A] | Poles | Rated current [A] | Rated operational voltage | Rated short circuit making capacity Icm [kA peak] | Rated short time withstand current Icw [kA] | Utilization category | Upstream breaker (OCPD) | Outline dimensions [mm] (HxWxD) | Weight [kg] |
|---|---|---|---|---|---|---|---|---|---|---|
| S160-SN | 160 | 3 / 4 | 160 | AC690V / DC250V | 2.8 | 2 (0.3sec) | AC-23A / DC-22A | E160-SJ | 75x130x68 / 100x130x68 | 0.7 / 0.9 |
| P160D | 160 | 3 / 4 | 160 | AC690V / DC250V | 2.8 | 2 (1sec) | AC-23A / DC-22A | P160F | 90x130x68 / 120x130x68 | 1.0 / 1.3 |
| S250-SN | 250 | 3 / 4 | 250 | AC690V / DC250V | 6 | 3 (0.3sec) | AC-23A / DC-22A | E250-SJ | 105x165x68 / 140x165x68 | 1.5 / 1.9 |
| P250D | 250 | 3 / 4 | 250 | AC690V / DC250V | 5 | 3.6 (1sec) | AC-23A / DC-22A | P250F | 105x165x68 / 140x165x68 | 1.5 / 2.0 |
| P400D | 400 | 3 / 4 | 400 | AC690V / DC250V | 7.6 | 5 (1sec) | AC-23A / DC-22A | P400N | 140x260x103 / 185x260x103 | 5.4 / 7.2 |
| P630D | 600 | 3 / 4 | 630 | AC690V / DC250V | 13 | 7.6 (1sec) | AC-23A / DC-22A | P630N | 140x260x103 / 185x260x103 | 5.7 / 7.7 |
| S800-NN | 800 | 3 / 4 | 800 | AC690V / DC250V | 17 | 10 (0.3sec) | AC-23A / DC-22A | S800-NJ | 210x273x103 / 280x273x103 | 8.5 / 11.5 |
| S1000-NN | 1000 | 3 / 4 | 1000 | AC690V / DC250V | 17 | 10 (0.3sec) | AC-23A / DC-22A | S1000-NE | 210x273x103 / 280x273x103 | 10.4 / 14.0 |
| S1250-NN | 1250 | 3 / 4 | 1250 | AC690V / DC250V | 32 | 15 (0.3sec) | AC-23A / DC-22A | S1250-NE | 210x370x120 / 280x370x120 | 18.2 / 23.4 |
| S1600-NN | 1600 | 3 / 4 | 1600 | AC690V / DC250V | 45 | 20 (0.3sec) | AC-23A / DC-22A | S1600-NE | 210x370x140 / 280x370x140 | 24.9 / 32.9 |
AC690V / AC-23A and DC250V / DC-22A are the two ratings of each type, joined with a slash. The outline dimensions are headed HxWxD on this page but follow the same order as the other tables. P630D is printed in the 600 A frame row with a rated current of 630 A.
Moulded case switch (circuit breaker without overcurrent trip mechanism) · 3 rows · Terasaki’s TemBreak PRO Non-automatic trip breakers page, ratings and specifications table (catalogue 23-I68E) · accessories: TemBreak PRO Accessories, TemBreak PRO Motor Operators
| Model | Frame [A] | Poles | Rated current [A] | Rated operational voltage | Rated short circuit making capacity Icm [kA peak] | Rated short time withstand current Icw [kA] | Max. switching current | Upstream breaker (OPCD) | Outline dimensions [mm] (WxHxD) | Weight [kg] |
|---|---|---|---|---|---|---|---|---|---|---|
| XS2000NN | 2000 | 3 / 4 | 2000 | AC690V / DC250V | 90 | 35 (0.3sec) | AC12000A / DC5000A | XS2000NE | 320×450×185 / 429×450×185 | 51.8 / 64.8 |
| XS2500NN | 2500 | 3 / 4 | 2500 | AC690V / DC250V | 90 | 35 (0.3sec) | AC15000A / DC6250A | XS2500NE | 320×450×185 / 429×450×185 | 60.0 / 75.7 |
| XS3200NN | 3200 | 3 | 3200 | AC690V / DC250V | 90 | 38 (0.5sec) | AC15000A / DC6250A | XS3200NE | 320×450×185 | 60.0 |
AC and DC values printed on two sub-rows are joined with a slash.
DC moulded case switch-disconnector · 13 rows · Terasaki’s TemBreak PRO 600-1000 V DC switch-disconnectors page, ratings and specifications table (catalogue 21-I73E)
| Model | Frame [A] | Poles | Rated current [A] | Rated operation voltage | Utilization category | Rated short time withstand current [kA/0.3sec] | Outline dimensions [mm] (WxW\HxD) | Weight [kg] |
|---|---|---|---|---|---|---|---|---|
| S160-SDN | 160 | 3 | 160 | DC600V | DC-22A | 2 | 75x130+50x68 | 0.8 |
| PVS160-SNL | 160 | 4 | 160 | DC800V | DC-22A | 3 | 140x165+110x68 | 1.9 |
| PVS160-SNH | 160 | 4 | 160 | DC1000V | DC-22A | 3 | 140x165+110x68 | 1.9 |
| S250-SDN | 250 | 3 | 250 | DC600V | DC-22A | 3 | 105x165+55x68 | 1.5 |
| PVS250-SNL | 250 | 3 | 250 | DC750V | DC-22A | 3 | 105x165+110x68 | 1.5 |
| PVS250-SNL | 250 | 4 | 250 | DC800V | DC-22A | 3 | 140x165+110x68 | 1.9 |
| PVS250-SNH | 250 | 4 | 250 | DC1000V | DC-22A | 3 | 140x165+110x68 | 1.9 |
| PVS400-NNL | 400 | 3 | 400 | DC750V | DC-22A | 5 | 140x260x103 | 4.2 |
| PVS400-NNL | 400 | 4 | 400 | DC800V | DC-22A | 5 | 185x260x103 | 5.6 |
| PVS400-NNH | 400 | 4 | 400 | DC1000V | DC-22A | 5 | 185x260x103 | 5.6 |
| PVS800-NNL | 800 | 3 | 630,800 | DC750V | DC-22A | 10 | 210x273x103 | 8.5 |
| PVS800-NNL | 800 | 4 | 630,800 | DC800V | DC-22A | 10 | 280x273x103 | 11.5 |
| PVS800-NNH | 800 | 4 | 630,800 | DC1000V | DC-22A | 10 | 280x273x103 | 11.5 |
Air switch-disconnector (AX…D) · 10 rows · Terasaki’s TemPower PRO page, switch disconnectors table (catalogue 25-I58E) · accessories: TemPower PRO ACB Accessories
| Model | Frame [A] | Poles | Maximum rated current [A] | Utilization category JIS C 8201-3 IEC60947-3 | Rated short circuit making capacity [kA peak] (AC440V) Icm | Rated short time withstand current Icw[kA] | Outline dimensions [mm] (W x H x D) | Weight [kg] for draw-out type |
|---|---|---|---|---|---|---|---|---|
| AX106D | 630 | 3 | 630 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX106D | 630 | 4 | 630 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX108D | 800 | 3 | 800 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX108D | 800 | 4 | 800 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX110D | 1000 | 3 | 1000 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX110D | 1000 | 4 | 1000 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX112D | 1250 | 3 | 1250 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX112D | 1250 | 4 | 1250 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
| AX116D | 1600 | 3 | 1600 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 276 x 312.5 x 240 / Draw-out type 288 x 322 x 340 | 37 |
| AX116D | 1600 | 4 | 1600 | AC-23 | 121 | AC690V 1s 55 / AC440V 1s 42 | Fixed type 346 x 312.5 x 240 / Draw-out type 358 x 322 x 340 | 45 |
Moulded case switch-disconnector (type NN, no protection) · 9 rows · Terasaki TemBreak 2 catalogue 18-I61E, switch-disconnector ratings (pp. 21 and 22)
| Model | Frame [A] | Poles | Ie [A] | Ue AC [V] | Ue DC [V] | Icm [kA peak] | Icw 0.3 s [kA rms] | Utilisation category (IEC 60947-3) |
|---|---|---|---|---|---|---|---|---|
| S125-NN | 125 | 3, 4 | 125 | 690 | 250 | 3.6 | 2 | AC-23A / DC-22A |
| S160-NN | 160 | 3, 4 | 160 | 690 | 250 | 6 | 3 | AC-23A / DC-22A |
| S250-NN | 250 | 3, 4 | 250 | 690 | 250 | 6 | 3 | AC-23A / DC-22A |
| S400-NN | 400 | 3, 4 | 400 | 690 | 250 | 9 | 5 | AC-23A / DC-22A |
| S630-NN | 630 | 3, 4 | 630 | 690 | 250 | 9 | 5 (3) | AC-23A / DC-22A |
| S800-NN | 800 | 3, 4 | 630, 800 | 690 | 250 | 17 | 10 | AC-23A / DC-22A |
| S1000-NN | 1000 | 3, 4 | 1000 | 690 | 250 | 17 | 10 | AC-23A / DC-22A |
| S1250-NN | 1250 | 3, 4 | 1250 | 690 | 250 | 32 | 15 | AC-23A / DC-22A |
| S1600-NN | 1600 | 3, 4 | 1600 | 690 | 250 | 45 | 20 | AC-23A / DC-22A |
From the earlier TemBreak 2 range, replaced by TemBreak PRO. Ask FMST which to order.
FMST quotes Terasaki switch-disconnectors and non-automatic breakers on request, because the rate depends on the model, rating and quantity. WhatsApp 0306 4758850 with the order code (for example PE30-NN and S160-SN) and FMST replies with the current rate.
TemBreak PRO Switch-disconnectors (20 models), TemBreak PRO European Switch disconnectors (10 models), TemBreak PRO Non-automatic trip breakers (3 models), TemBreak PRO Switch-disconnectors 600-1000 V DC (13 models), TemPower PRO Switch Disconnectors (10 models) and TemBreak 2 Switch-Disconnectors (9 models): 6 families and 65 models, each row as Terasaki’s own catalogues and product pages print it.
TemBreak PRO Switch-disconnectors (moulded case switch-disconnector (no overcurrent trip)), TemBreak PRO European Switch disconnectors (moulded case switch-disconnector), TemBreak PRO Non-automatic trip breakers (moulded case switch (circuit breaker without overcurrent trip mechanism)), TemBreak PRO Switch-disconnectors 600-1000 V DC (DC moulded case switch-disconnector), TemPower PRO Switch Disconnectors (air switch-disconnector (AX…D)) and TemBreak 2 Switch-Disconnectors (moulded case switch-disconnector (type NN, no protection)).
Yes. FMST (Finest Material Supplier & Traders) is an Authorized Partner & Distributor of Terasaki in Lahore, supplying genuine Terasaki switch-disconnectors and non-automatic breakers to contractors, panel builders, developers and buyers across Pakistan. WhatsApp 0306 4758850 with your list.
WhatsApp the order codes from this page, or your load list, and FMST quotes genuine Terasaki. Electrical desk: 0306 4758850. All Terasaki categories: Terasaki circuit breakers.